Automatic Tank Gauge (ATG): How Underground Tank Monitoring Works

Rakimni Solutions Ltd · Published 9 November 2026 · Updated 20 November 2026 · 7 min read

An underground tank hides its contents. The traditional answer is a dip stick: open the chamber, lower the stick, read the wet line, write it down. It works, but it gives one coarse reading when someone remembers to take it. An automatic tank gauge (ATG), also called an automatic tank gauging system, gives you the reading continuously.

What is an ATG system?

An ATG system has two parts: a probe installed in each tank and a console or software that collects the probe data. The probe measures the fuel level, and typically also the water level at the bottom of the tank and the fuel temperature. The software converts level into volume using the tank's calibration chart.

ATG probe and sensors: how they work

People use "ATG probe" and "ATG sensor" loosely. In practice the probe is the whole rod assembly that hangs in the tank, and the sensors are the measuring elements on it.

  • Fuel level: a float rides on the probe shaft at the fuel surface. In the most widely used design, the magnetostrictive probe, a pulse sent along the shaft reacts with a magnet in the float, and the time taken for the return signal gives the float's position very precisely.
  • Water level: a second float, weighted to sit at the fuel and water boundary, reports how much water has collected at the bottom of the tank. Water floats are made for a specific fuel: a diesel float is heavier than a petrol one, and they are not interchangeable. A petrol float in a diesel tank will not sink through the diesel to the water, which produces unusually high water readings and can interfere with the product float.
  • Temperature: one or more temperature sensors along the shaft (some probes carry up to five) report fuel temperature, which allows volume to be corrected to a reference temperature such as 15 or 20 degrees Celsius on systems that support it.

Where the probe goes in the tank

Placement affects accuracy. Manufacturer guidance for a widely used probe family is to install the probe near the centre of the tank and roughly 0.9 m (3 ft) or more from the fill pipe and from the submersible pump. Closer than that, the force of fuel entering the tank or being drawn out can push the water float up the shaft and cause a false high-water alarm or distorted readings. If the tank is tilted, the probe's position relative to the centre needs a product offset correction, worked out from dip readings taken at two points in the tank. The probe itself normally sits in a riser pipe on the tank opening.

How the probe connects to the console

The probe is wired to the console in the station. In many systems the console supplies low-voltage power (12 V DC in one widely used design) through an intrinsically safe barrier, so no spark-capable energy reaches the tank. The probe sends its readings back to the console over the cable. The console applies the tank calibration chart to turn level into litres, records the data and raises alarms, and many consoles can pass data on to software or remote monitoring.

Two practical points. The console itself must sit in a safe area, outside the hazardous zone. And probe cables must be sealed where they enter the conduit before the barrier, because explosive fumes can travel along a cable jacket. Installation and wiring should be done by a qualified installer to the standards that apply to your site.

What to check when choosing or auditing probes

  • Probe length matches the depth of the tank.
  • The water float is the correct type for the fuel in that tank (diesel or petrol).
  • The probe is a certified type for the hazardous zone, and compatible with your console and software.
  • The probe is clear of the fill pipe and pump, and offset is set if the tank is tilted.
  • The tank calibration chart is correct for that specific tank.

What an ATG tells you

  • Current stock by tank, in litres, without opening a chamber.
  • Delivery quantities: the measured rise in level during a delivery, to compare with the delivery note.
  • Water presence: water in a tank damages engines and costs money. Early detection lets you act before contaminated fuel is sold.
  • Temperature: useful because fuel volume changes with temperature, which affects reconciliation accuracy.
  • Stock trend: how quickly a tank is drawing down, which supports reordering and exposes unexplained drops.

How an ATG feeds fuel stock reconciliation

Reconciliation compares three records of the same fuel: what the tank lost, what the pumps metered and what sales recorded. The ATG supplies the first record, and supplies it better than a dip stick does. Opening stock, closing stock and delivery quantities come from timestamped gauge readings instead of whoever happened to dip the tank.

  1. Take opening stock from the gauge at the start of the day.
  2. Add deliveries, using the gauge-measured quantity, not only the delivery note.
  3. Subtract closing stock from the gauge. The result is the tank drawdown.
  4. Compare the drawdown with the pump meter totals, then compare the pump totals with recorded sales.
  5. Investigate gaps by tank, pump, shift and delivery.

Full reconciliation also needs dispenser or POS sales data connected and mapped to the right tank. Some consoles then produce hourly loss-rate, daily variance and 30-day summary reports; without the sales side you only have the tank half of the picture. Record test vends and pump calibrations too: fuel drawn from the tank to calibrate a meter has no matching sale and should not be read as loss.

Illustrative example (invented numbers, for explanation only): the gauge shows 20,000 litres at opening, no delivery, and 15,000 litres at closing, so the tank drawdown is 5,000 litres. Pump meters show 4,960 litres and recorded sales show 4,950. The tank-to-pump gap is 40 litres (about 0.8% of metered volume) and the pump-to-sales gap is 10 litres. The two gaps point to different causes, which is why the three records are compared separately. The full method is in our daily fuel reconciliation guide.

Free fuel reconciliation template (Excel)

A ready-to-use workbook with the daily reconciliation formulas above and a delivery verification sheet. Enter your readings and it calculates drawdown, variances and flags days to investigate. You set your own threshold.

↓ Download the free template (.xlsx)

How ATG systems reduce fuel loss

Modern ATG systems reduce loss by making it visible quickly and traceable to a point in time. The main mechanisms are:

  • Continuous measurement: a drop in level while no pump is dispensing shows up with a timestamp, so you can ask what happened at that hour instead of that month. Some consoles log every tank's reading every minute, so the history shows when a drop began. Some also let you set a loss warning, a loss alarm and a quiet-period alarm for loss when no sales are expected.
  • Delivery verification: a gauge-measured quantity next to the delivery note catches short deliveries on the day they happen. The console detects a delivery when level rises past a set quantity and waits for a settling period before trusting readings, because turbulence after a delivery distorts them (one manufacturer recommends about 100 litres to start detection and about 5 minutes to settle). Some consoles compare against the delivery note automatically only if you enter the book quantity. Many sites do this comparison by hand, which is what the delivery sheet in the free template is for.
  • Water alarms: catching water early stops contaminated fuel being sold and the claims and write-offs that follow.
  • Trend and leak alarms: on systems that support them, a slow unexplained decline can be caught before it becomes a large loss.
  • Remote alerts: connected systems push alarms and readings to software or a phone, so the person responsible does not have to be on site to see a problem.

Illustrative example (invented numbers): a supplier delivery note says 10,000 litres. The gauge reads 4,000 litres before and 13,960 litres after, with no sales during the delivery. Measured receipt is 9,960 litres, 40 litres (0.4%) below the note. Whether that is a shortfall or temperature and settling is for you to judge against your own baseline, but you now have a record to raise with the supplier.

One limit matters here. An ATG measures; it does not stop anyone taking fuel. Loss falls only when the alerts and variances are reviewed and acted on. We do not quote a standard percentage reduction, because results depend on the site, the starting level of control and follow-through.

Leak detection

Some ATG systems run static leak tests, typically at a stated leak rate such as 0.1 or 0.2 US gallons per hour under the US EPA procedure. The tank must be idle for a period of hours, above a minimum fill level, and not just after a delivery, and any sale or delivery during the test aborts it. Ground vibration, heavy evaporation, a faulty probe or sticky float, and incorrect tank charts can all affect the result. Exact conditions vary by console, so confirm what your system supports and what your regulator or insurer expects before relying on it.

ATG limits to understand

  • Accuracy depends on correct tank calibration charts. A wrong chart gives precise but wrong volumes.
  • Probes and consoles need maintenance and periodic verification against a manual dip.
  • A probe too close to the fill pipe or pump can give false high-water alarms and distorted readings.
  • A sticky float or the wrong water float gives wrong water and product readings.
  • An ATG alone does not say who dispensed the fuel. It needs pump, attendant and sales data beside it.

Connecting the ATG to everything else

The strongest setup combines tank gauging with pump readings, attendant tags and daily sales. Then the tank figure, the pump figure and the sales figure are reconciled automatically every day, and variance is traced to a tank, pump, shift or person. Start with daily fuel reconciliation and daily sales monitoring.

See our fuel management solution for how tank gauging, vehicle ID, attendant tagging and sales monitoring fit together.

ATG questions answered

What data does an automatic tank gauge provide?
An automatic tank gauge provides current fuel stock by tank in litres, the water level at the bottom of the tank, fuel temperature, the measured rise in level during a delivery, and the rate at which stock is drawing down. Many systems also raise alarms for water, low stock and unexplained drops.
What is an ATG probe?
An ATG probe is the rod-shaped assembly installed vertically in a fuel tank. It carries sensors for fuel level, water level and temperature, and sends its readings by cable to the ATG console. The most widely used type is the magnetostrictive probe.
How do ATG systems help with fuel stock reconciliation?
An ATG gives accurate opening stock, closing stock and delivery quantities for each tank. Those figures produce the tank drawdown, which is compared with pump meter totals and recorded sales. Any gap is then traced to a tank, pump, shift or delivery.
How do modern ATG systems reduce fuel loss?
Modern ATG systems measure tanks continuously, flag unexplained drops with a timestamp, check delivery quantities against delivery notes, detect water, and send alerts to software or phones. They reduce loss only when someone acts on the alerts: an ATG measures, it does not prevent theft by itself.